Heat Pumps
Heat Pump Defrost Cycles Ontario 2026: What Homeowners Should Expect
Every air-source heat pump in Ontario runs defrost cycles all winter. The outdoor unit blows steam, the fan stops, the compressor runs in reverse for a few minutes, and electric-resistance backup carries the heating load until the coil is clear. It looks alarming the first time. This guide covers what is happening, what is normal, what is not, how long cycles should last, how often they should run, what the warning signs of a broken defrost look like, and what a repair typically costs.
Key Takeaways
- Outdoor coils frost up in winter because the coil runs colder than the air around it. That is physics, not a defect.
- Defrost is the reversing valve flipping the unit into cooling mode for 3 to 10 minutes to warm the outdoor coil and melt the frost.
- Electric-resistance supplemental heat keeps the house warm during defrost. The fan on the outdoor unit stops.
- Typical frequency is every 30 to 90 minutes depending on temperature and humidity.
- Steam (white vapour) rising from the outdoor unit during defrost is water, not smoke.
- NEEP-listed cold-climate heat pumps use demand defrost, which runs 30 to 50 percent fewer cycles than timed defrost.
- Solid ice filling the fan shroud or sealing the base pan, supplemental heat that never shuts off, and a hydro bill 40 percent higher than last winter are the three signs of a broken defrost.
Why an Outdoor Coil Ices Up
A heat pump moves heat from outdoor air into the house. To do that, refrigerant in the outdoor coil must be colder than the ambient air so heat flows into it.[2]In Ontario winters the outdoor coil often operates at minus 10 to minus 20 Celsius even when the ambient air is closer to zero. Any moisture in the air that touches the coil freezes on the aluminum fins. The colder the coil and the higher the outdoor humidity, the faster frost builds.
Frost insulates the coil and blocks airflow, so heat transfer drops. Left alone, the unit would ice shut and stop heating within an hour or two. The defrost cycle is the designed response.[4]
How Reverse-Valve Defrost Works
When the defrost control board decides it is time to clear the coil, it commands the reversing valve to flip. The heat pump runs in cooling mode for a few minutes: hot refrigerant is routed to the outdoor coil instead of the indoor coil. The outdoor coil warms rapidly and the frost melts and runs off as water into the base pan.[4]During defrost:
- The outdoor fan stops so the coil heats faster and the warm air does not blow away.
- Steam (water vapour from melting frost meeting cold air) rises from the cabinet. This is not smoke or refrigerant.
- The indoor coil would blow cold air for the duration of the cycle, so electric-resistance supplemental heat energizes to keep supply air warm.
The cycle ends when the coil sensor sees the coil warm above the termination setpoint (typically 10 to 15 Celsius) or when a maximum time has elapsed. The reversing valve flips back and normal heating resumes.
Electric-Resistance Supplemental Heat
Nearly every cold-climate heat pump installed in Ontario includes electric-resistance backup heat, usually a strip heater in the air handler or the furnace's auxiliary bank. During defrost the indoor coil is being cooled rather than heated, so without supplemental heat the supply air would be uncomfortably cold for several minutes. The strip heat typically adds 5 to 20 kW depending on system size and is expensive to run. The defrost control limits supplemental heat to the defrost duration plus a short recovery.
Supplemental heat is also what carries the house through outdoor temperatures below the unit's rated low-ambient limit. A properly commissioned system switches to backup only during defrost and during design-day extremes. A system riding on supplemental heat for hours at moderate outdoor temperatures is a sign the heat pump side has failed and the defrost loop is often the cause.
Typical Defrost Duration and Frequency
A healthy defrost cycle runs 3 to 10 minutes and terminates when the coil sensor confirms the coil is clear.[4]Frequency scales with how fast frost builds, which scales with humidity and temperature:
| Outdoor Conditions | Typical Defrost Interval | Why |
|---|---|---|
| Minus 5 to plus 2 Celsius, wet snow or high humidity | Every 30 to 45 minutes | Warmest air holds the most moisture; fastest frost buildup |
| Minus 5 to minus 10 Celsius, dry air | Every 60 to 90 minutes | Moderate humidity; moderate buildup |
| Colder than minus 15 Celsius | Every 90 to 120 minutes or less often | Cold air holds very little moisture; slow buildup |
| Warmer than plus 5 Celsius | Rarely | Coil is above freezing most of the time |
These ranges hold for most NEEP-listed cold-climate units sold in Ontario.[1]Short bursts of wet snow followed by a drop in temperature can trigger a defrost every 20 to 30 minutes for an hour or two, which is normal for the conditions. A unit defrosting every 15 minutes continuously for an entire day in steady weather is not.
Normal Versus Abnormal Ice Patterns
Healthy frost looks like a uniform white layer across the face of the outdoor coil, 1 to 4 mm thick, with the bottom of the cabinet clear and drain holes in the base pan flowing. The fan blade spins freely with a small amount of frost on the guard. Ice patterns that warrant a service call look different:
- Solid clear ice block on the lower cabinet:drain holes are blocked, melt water cannot escape, and it refreezes between cycles. Fix the drainage; if the base pan heater has failed, that is the cause.
- Ice inside the fan shroud or on the blade:usually a failed defrost initiation (the unit never defrosts) or a stuck reversing valve (defrost runs but the coil does not warm).
- Coil iced white for hours with no signs of defrost: defrost board, coil temperature sensor, or outdoor ambient sensor has failed. Supplemental heat is carrying the load.
- One side of the coil iced, the other clear:refrigerant distribution problem, low charge, or a partially blocked distributor. Needs a pressure and superheat check.
- Ice dam on a rooftop or overhang above the unit: melt water refreezes on the unit below. Fix the drip or add a deflector; do not chip ice off the unit.
Demand Defrost Versus Timed Defrost
Older heat pumps used timed defrost: a clock initiated a cycle on a fixed schedule (every 30, 60, or 90 minutes) whenever outdoor temperature dropped below a setpoint, regardless of whether frost had actually built up. That meant unnecessary cycles on cold, dry days and unnecessary supplemental heat events.
Demand defrost (also called smart or adaptive defrost) uses sensors to decide when to defrost. The control board watches coil temperature against outdoor ambient and may also watch pressure drop across the coil as frost thickens. It triggers a cycle only when the coil shows measurable frost loading. Most NEEP-listed cold-climate heat pumps (Mitsubishi Hyper-Heat, Daikin Aurora, LG, Fujitsu, Carrier Greenspeed, and others) ship with demand defrost as standard.[6]In Ontario conditions demand defrost typically cuts cycle counts 30 to 50 percent compared to timed defrost, with a corresponding drop in supplemental-heat runtime and winter hydro consumption.[8]
Why NEEP-Listed Cold-Climate Units Defrost More Efficiently
NEEP maintains the Cold Climate Air Source Heat Pump product list, which certifies units that deliver specified capacity and COP at minus 15 Celsius and below.[1]Cold-climate units use larger outdoor coils with wider fin spacing, inverter-driven compressors that can modulate capacity instead of cycling on and off, and demand defrost control logic. Larger coil surface area means each cycle melts more frost in less time. Wider fin spacing means frost accumulates more slowly and takes longer to block airflow. Variable-speed compressors can run at partial capacity on mild days, keeping the coil warmer and delaying frost formation.[6]The combined effect is fewer, shorter defrost cycles and less supplemental heat, which is the difference that shows up on the January hydro bill.
Steam, Fog, and What Is Not Smoke
The plume that rises from the outdoor unit during defrost is water vapour condensing in cold air. The melting frost becomes water, the warm cabinet evaporates some of it, and the vapour meets cold outside air and forms visible fog. It has no smell, dissipates in seconds, and stops when the cycle ends. It is not smoke and not refrigerant leakage.[2]
Actual warning signs that involve the outdoor unit: an electrical or burning-plastic smell, black smoke rather than white vapour, a hissing sound that persists after the cycle ends (possible refrigerant leak), or oil streaks near line-set connections. Any of those warrants shutting the unit off at the disconnect and calling service.
Snow Drift and Clearance Requirements
Manufacturers publish clearance requirements so defrost melt water drains, airflow is unobstructed, and the unit is above the typical snow line. A common Ontario spec:
- Minimum 12 inches above grade or snow line:the unit must sit on a riser or pad tall enough to stay above drifts. Snow melting from a drift directly on the cabinet will re-ice the unit.
- Minimum 24 inches of clearance around the sides and front: airflow into the coil cannot be blocked by fences, shrubs, wall returns, or snow piles.
- Minimum 48 inches above the unit if there is an overhang: roof drip lines that drop water or snow onto the unit cause the most expensive ice damage.
- Not under a rainspout or downspout: the unit is not a splash block.
If the installer placed the unit in a spot that violates these clearances, that is an install defect, not a homeowner problem. Short of relocating the unit, a snow riser and an overhang deflector are usually the fix.
Signs the Defrost Is Actually Broken
Three signs together, not one in isolation, mean call service:
- Coil stays solidly iced for hours: you can see the outdoor coil is white or blue-ice and no defrost cycle is audibly starting. The fan keeps trying to spin against frost or is stuck.
- Supplemental or auxiliary heat runs continuously: the thermostat shows "AUX" or "Em Heat" on for hours instead of minutes. The heat pump side has effectively stopped contributing and the house is being heated by electric strips only.
- Hydro bill jumps 40 to 100 percent in January or February compared to the same month in the previous year. Electric-resistance heat uses roughly 2 to 3 times as much electricity per BTU as a working heat pump.[8]
Individually these can be weather, thermostat settings, or a dirty filter. Together they mean the defrost control board, a coil sensor, the reversing valve, or the outdoor fan motor has failed. Running on supplemental heat costs money every hour it continues, so this is not a wait-and-see diagnosis.
Typical Defrost Repair Costs
Ontario 2026 pricing for the most common defrost-related repairs on a residential air-source heat pump:
| Component | Part Cost | Installed Cost |
|---|---|---|
| Defrost control board | $150 to $350 | $300 to $650 |
| Coil temperature sensor / thermistor | $60 to $120 | $200 to $350 |
| Outdoor ambient sensor | $40 to $100 | $180 to $300 |
| Reversing valve (with recover and recharge) | $200 to $500 | $600 to $1,200 |
| Outdoor fan motor (ECM) | $250 to $600 | $500 to $1,000 |
| Base pan heater | $50 to $150 | $200 to $400 |
Parts are often covered by manufacturer warranty on units under 10 years old; labour is usually not unless you bought an extended labour warranty. That is why most out-of-pocket defrost repairs land between $200 and $500 even on warrantied units.
When to Call Service Versus Wait It Out
Wait it out: a defrost cycle running right now with steam rising and the fan stopped; thin white frost across the coil between cycles; more frequent cycles than usual after a wet-snow event (give it a day); house maintaining setpoint with supplemental heat cycling only briefly during defrost.
Call service: coil solidly iced for hours with no defrost activity; Aux or Em Heat on the thermostat for hours at a time; house not reaching setpoint on a day that is not extraordinarily cold; electrical smell, oil streaks, or persistent hissing after a cycle; visible ice inside the fan shroud or on the blade; a winter hydro bill more than 40 percent above the same month last year.
On a multi-zone ductless heat pump, a failure on one outdoor condenser can still leave other zones heating, which sometimes masks the problem. Check every indoor head during a suspected defrost failure, not just the one you notice. See our related guide on cold-climate heat pump selection for NEEP-listed units that are designed for the conditions that drive defrost the hardest, and our HVAC commissioning guide for the measurements that catch a failing defrost loop at install time.
Frequently Asked Questions
Is it normal for my heat pump to blow steam and stop heating in the middle of winter?
Yes. Every air-source heat pump runs a defrost cycle every 30 to 90 minutes in cold, damp Ontario weather. The outdoor unit temporarily switches to cooling mode to warm its own coil and melt the frost, which is why you see steam rising from the cabinet and the fan stops. The indoor unit keeps blowing heat because electric-resistance supplemental heat energizes during the cycle. A normal defrost lasts 3 to 10 minutes. If it runs longer than 15 minutes or repeats back-to-back without a full heating run between, that is a problem.
Why does my heat pump ice up outside? Is that broken?
Frost on the outdoor coil is normal and expected in Ontario winters. The outdoor coil runs colder than ambient air to absorb heat, so any humidity in the air freezes on the fins. Thin, even frost across the coil is healthy. A solid block of clear ice covering the bottom of the cabinet, ice filling the fan shroud, or a skirt of ice sealing the base pan is not. The first is humidity freezing during normal operation. The second is a drainage, defrost-sensor, or reversing-valve problem and needs service.
How often should a heat pump defrost in cold Ontario weather?
In the most demanding conditions, around minus 5 to plus 2 Celsius with high humidity or wet snow, expect a defrost every 30 to 45 minutes. Below minus 10 Celsius the air holds less moisture and defrost frequency drops to every 60 to 90 minutes. Above plus 5 Celsius most units rarely defrost at all. Modern demand-defrost controls watch coil temperature and pressure drop across the fins and only trigger when needed, so cycle counts vary with weather, not a fixed clock.
What is the difference between timed defrost and demand defrost?
Timed defrost runs a cycle on a fixed schedule, typically every 30, 60, or 90 minutes whenever the outdoor temperature is below a setpoint, regardless of whether frost has actually built up. Demand defrost (also called smart defrost or adaptive defrost) measures coil temperature and airflow pressure and only triggers when frost restricts the coil. Demand defrost can cut unnecessary cycles by 30 to 50 percent in Ontario conditions, which translates to fewer supplemental-heat events and a lower winter hydro bill. Most NEEP-listed cold-climate heat pumps use demand defrost.
How do I know if my defrost is actually broken?
Three signs together mean service: the outdoor coil stays solidly iced for hours even after you hear the unit try to defrost, the supplemental or auxiliary heat light on the thermostat stays on continuously, and your hydro bill for January or February is 40 to 100 percent higher than the same month last year. Individually any one can be weather or thermostat settings. Together they mean the defrost board, reversing valve, or a sensor has failed and the unit is riding on electric-resistance backup, which is 2 to 3 times more expensive than heat pump operation.
What does it cost to repair a broken defrost on a heat pump?
A defrost control board is typically $150 to $350 for the part plus $150 to $300 labour for a total of $300 to $650 installed. A defrost thermistor or coil temperature sensor is cheaper, often $60 to $120 for the part plus labour. A failed reversing valve is the expensive scenario at $600 to $1,200 installed because the refrigerant has to be recovered, the valve brazed in, and the system evacuated and recharged. On units under warranty the part is typically covered and labour is usually not, which is why the out-of-pocket cost rarely drops below $200 even on warranty repairs.
Related Guides
- Cold Climate Heat Pump Ontario 2026
- HVAC Commissioning and Testing Ontario 2026
- HVAC Noise Bylaws Ontario 2026
- Northeast Energy Efficiency Partnerships (NEEP) Cold Climate Air Source Heat Pump (ccASHP) Specification and Product List
- Natural Resources Canada Heating and Cooling With a Heat Pump (homeowner guide)
- Heating, Refrigeration and Air Conditioning Institute of Canada (HRAI) Residential Heat Pump Installation and Service Guidance
- American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) ASHRAE Handbook: HVAC Systems and Equipment, Chapter on Air-Source Heat Pumps and Defrost Control
- Canadian Standards Association (CSA) CSA F280-12 Determining the Required Capacity of Residential Space Heating and Cooling Appliances
- Mitsubishi Electric Trane HVAC US Hyper-Heating INVERTER (H2i) Engineering and Service Manuals
- Daikin Industries Aurora Series Cold-Climate Heat Pump Technical Data and Service Documentation
- Ontario Energy Board Residential Electricity Prices and Time-of-Use Rates
- ENERGY STAR Canada ENERGY STAR Certified Air-Source Heat Pumps: Performance Criteria and Installation Requirements